Abstract To increase the power rating and reduce the cost and complexity of a multi-pulse rectifier (MPR), it is well known that the pulse number must be increased. In some practical cases, a 12-pulse rectifier (12PR) is suggested as a good solution considering its relatively simple structure and low weight. However, 12-pulse rectifiers cannot technically meet the stan- dards of harmonic distortion requirements for some industrial applications, and therefore they must be used along with output filters. Two cost-effective 24-pulse rectifiers (24PRs) are suggested in the article, which consist of a polygon autotransformer 12PR and two pulse doubling circuits (PDCs) at dc link. The first PDC (PDC1) is based on an inter- phase transformer (IPT) with a step-up secondary winding, and the second one (PDC2) is based on an IPT with a step-down secondary winding. To show the advantages of the pro- posed combinations compared with other solutions, simulation results are used, and also a prototype is implemented to evaluate and verify the simulation results. The simulation and experimental test results show that the total harmonic distortion (%THD) of the input current for the 12PR with PDC1 is less than 3.67%, and the 12PR with PDC2 is less than 1.45%, which meets the IEEE 519 and DO-160G requirements. Also, it is shown that in comparison with other solutions, the proposed two configurations are cost-effective, power factor is near unity, rating is almost 29% of the load rating, and the efficiency is almost 97.5%, which makes them a practical solution for more electric aircraft.

کلید واژگان :

Total harmonic distortion (THD)