چکیده :

Optimization can be defined as the use of the specific methods to determine the most effective and economical solution to a problem in a process. Optimization is one of the most important decision-making tools in the industry. Optimization uses the effective quantity methods by choosing the best answer or solution among the possible solutions. Of course, computers and the related software have made the necessary calculations feasible with the least cost. In this paper, an energy optimization has been done for condensations stabilization unit of Ilam gas refinery (IGTP). At first, the stabilization unit has been simulated and examined in the environment of the commercial HYSYS Refinery software by taking into account all the details. Then, it has been defined by using integration techniques and scenario processing facilities with the purpose of losing Electricity consumption. Again, the presented scenario was defined in the software. The obtained results from the simulation reveal that in case of using feed stream as the energy integration factor (for cooling) and using heat exchanger Instead of the present air conditioner, 1/1 Mega Watt electric power will be saved in addition to the omission air conditioner 1060/1360 AC (this equipment is currently being used for cooling) and the reduction of operating costs amounted to be more than $ 522,240 a year

کلید واژگان :

Air Conditioner, Energy Efficiency, Energy Integration, Gas Refinery, Heat Exchanger



ارزش ریالی : 1200000 ریال
دریافت مقاله
با پرداخت الکترونیک