چکیده :

In this paper, a new multi‐pulse clean power converter topology is presented with lower than 3% input current total harmonic distortion (THD). The topol- ogy is based on the combination of a 36‐pulse converter and a pulse doubling circuit. The 36‐pulse converter consists of a “polygon” autotransformer and two 18‐pulse diode bridge rectifiers. Pulse doubling circuit consists of zero‐ sequence‐blocking transformer (ZSBT) and tapped interphase transformer (IPT). The important advantage of the proposed AC‐DC converter is consider- able reduction in burdens of the magnetic parts with respect to the nominal load rating. It provides more economical solution to achieve harmonic mitiga- tion in electric power systems as compared with other 72‐pulse AC‐DC con- verters. The simulation and experimental results show that the input current THD is less than 3% using the proposed topology. The results indicate a signif- icant reduction in the total cost and volume of the proposed 72‐pulse configu- ration in comparison with similar configurations. Also, it is shown that the proposed converter rating is about 44% of the DC load power.

کلید واژگان :

72‐pulse converter, AC‐DC converter, polygon autotransformer, power quality, pulse doubling circuit



ارزش ریالی : 500000 ریال
دریافت مقاله
با پرداخت الکترونیک